Work backwards from what you use
Every number in an off-grid system derives from daily energy consumption, and it is the one figure worth measuring rather than estimating. List every load with its watts and the hours per day it actually runs:
| Load | Watts | Hours/day | Wh/day |
|---|---|---|---|
| 12 V compressor fridge | 45 | 10 | 450 |
| LED lighting, 6 fixtures | 30 | 5 | 150 |
| Laptop and phones | 60 | 4 | 240 |
| Water pump | 60 | 0.5 | 30 |
| Induction hob | 1500 | 0.5 | 750 |
| Total | 1620 Wh |
A clamp meter or a shunt-based battery monitor beats any spreadsheet, because measured consumption is invariably higher than estimated consumption.
The chain from load to nameplate
DC energy per day = AC energy ÷ inverter efficiency
usable energy = DC per day × days of autonomy
nameplate = usable ÷ depth of discharge ÷ round-trip efficiency
amp-hours = nameplate ÷ bank voltage
Two of those divisions are where calculators quietly diverge. You cannot use all of a battery, and you do not get back everything you put in. Both losses expand the nameplate you have to buy, and a tool that assumes 100 % depth of discharge produces an answer roughly half the size it should be.
Choosing a bank voltage
Bank voltage does not change how much energy you need. It changes every current downstream, and therefore what your cables and devices cost.
| Bank | Suits | Watch out for |
|---|---|---|
| 12 V | Under about 1500 W continuous. Vans, small cabins, anywhere 12 V appliances dominate. | Cable cost climbs fast. A 2000 W inverter pulls 185 A. |
| 24 V | Up to roughly 3 kW. Mid-size cabins and larger RVs. | You will need a DC-DC converter for 12 V appliances. |
| 48 V | 3 kW and above, and anything that might grow. | Widest modern component choice; server-rack LiFePO4 and hybrid inverters are built around it. |
Chemistry, honestly
LiFePO4 costs more per nameplate amp-hour and less per usable amp-hour, because you can use 80 % or more of it and it survives thousands of cycles doing so. It is lighter, needs no ventilation, and holds voltage far flatter under load. Its weakness is charging below freezing, which a good BMS blocks and which matters in an unheated space.
AGM is sealed, needs no maintenance, tolerates being mounted in more orientations, and is cheaper up front. Designed to 50 % depth, its usable capacity per dollar is worse than it looks.
Flooded lead-acid is the cheapest per nameplate amp-hour and the most demanding: ventilation for hydrogen, periodic watering, and an equalisation charge. In a stationary bank with someone willing to maintain it, the economics can still work.
What this calculator does not decide
Maximum continuous discharge current is a battery specification, not a capacity calculation. A 100 Ah LiFePO4 pack rated at 100 A continuous cannot feed a 3000 W inverter on a 12 V bus, which needs about 280 A, no matter how many watt-hours it stores. Check that figure on the datasheet alongside the capacity you calculate here, and size the battery-side conductors and protection to it.
