Skip to main content
SolarCalcWorks

Solar Voltage Drop Calculator

Enter the wire you already have and see exactly what it costs you. This calculator also checks the same conductor against NEC ampacity — because a wire can have a perfect voltage drop and still be too small to carry the current safely, and no other drop calculator tells you that.

  • DC 12 V · 24 V · 48 V · custom
  • NEC ampacity check included
  • Tells you what to change
  • Full working shown

Solar Voltage Drop Calculator

Inputs3 % target
System voltage
Conductor material

3% of 12 V = 0.36 V of budget across the whole round trip.

Installation conditionsdefaults are code-safe

These affect the NEC ampacity check, not the voltage drop itself. Drop is calculated from the Chapter 9 Table 8 resistance at its 75 °C reference.

Drop on 10 AWG5.3 mm²

8.27%0.99 V lost

Over the recommended limit

Above the 3 % that NEC 210.19(A) Informational Note 4 recommends. Not a code violation — voltage drop is advisory — but the equipment will feel it.

At the load
11.01 V
from 12 V
Lost as heat
20 W
8.3% of what you send
Loop resistance
0.0496 Ω
1.2400 Ω/kft
Max run at this size
7.3 ft
to hold 3.0%
Three ways to fix thisexact for your numbers
  1. Use a bigger conductor

    4 AWG is the smallest size meeting both your 3.0% target and NEC ampacity, at 2.05%. 3 sizes up from yours. Size it properly →

  2. Shorten the run

    10 AWG holds your target up to 7.3 ft one way.

  3. Raise the system voltage

    The same power at 24 V would drop just 2.07% on this wire. Doubling voltage halves the current and doubles the volts you can afford to lose, so the drop falls by a factor of four.

Calculation

1Loop resistance

2 × 20.0 ft × 1.2400 Ω/kft ÷ 1000 = 0.0496 Ω

The run is doubled because current returns on the second conductor. Resistance from NEC Chapter 9, Table 8, stranded at 75 °C.

2Voltage lost

20 A × 0.0496 Ω = 0.99 V

Ohm's law. Nothing else is involved on a DC circuit.

3As a percentage

0.99 V ÷ 12 V = 8.27%

This figure is also your efficiency loss: a 5 % drop turns 5 % of your power into heat in the wire. NEC 210.19(A) Informational Note 4 recommends 3 % or less, advisory.

4Ampacity — the separate, mandatory check

40 A @ 90 °C = 40 A
at terminals (75 °C): 35 A
needs 20 A derated, 25 A at terminals ✓

Two tests, both mandatory. This is the check most voltage drop calculators leave out entirely.

Reference 210.19(A)(1) · 310.15 · 110.14(C) · Ch.9 T.8 — NEC 2023. Voltage drop is a design target, not a code requirement. Sources and limitations.

Other sizes20 A · 20 ft · 12 V
Voltage drop by conductor size for this circuit
SizeDropVolts lostvs 3.0%
14 AWG20.93%2.51 VOver
12 AWG13.20%1.58 VOver
10 AWGyours8.27%0.99 VOver
8 AWG5.19%0.62 VOver
6 AWG3.27%0.39 VOver
4 AWG2.05%0.25 VMeets it

Voltage drop only. A size can meet this target and still fail NEC ampacity.

What voltage drop actually is

Every conductor has resistance. Push current through it and some of your voltage is spent pushing rather than arriving — converted to heat along the way. What reaches the load is what is left.

Vdrop = 2 × L × I × R ÷ 1000 — L is the one-way length in feet, I the current in amps, R the resistance in ohms per 1000 ft

The 2 is there because the current has to come back. A 20 ft run is 40 ft of copper in the loop, and both conductors drop voltage. R comes from NEC Chapter 9, Table 8, which publishes DC resistance directly — so on a DC circuit this is exact, with no power factor or reactance term to estimate.

It is a design target, not a code requirement

Voltage drop limits are not enforceable NEC requirements. NEC 210.19(A) Informational Note 4 and 215.2(A)(2) Informational Note 2 recommend a maximum of 3 % on a branch circuit or feeder and 5 % total. Informational notes are advisory.

That matters practically. An inspector will not fail an installation for a 4 % drop, but your charge controller will still undercharge the bank. Voltage drop is your problem to manage, which is different from someone else’s rule to satisfy — and it is why this calculator separates the drop verdict from the ampacity verdict rather than blending them into one pass or fail.

The targets worth using

Circuit Target Why
Charge controller to battery 2 % or less The controller senses battery voltage at its own terminals. Drop here makes it read high, end absorption early and chronically undercharge the bank.
Battery to inverter 2 % or less Highest current in the system. Drop shows up as premature low-voltage cutout and reduced surge capability.
Array to charge controller 3 % Usually the longest run. An MPPT controller recovers some loss by converting excess voltage, but it cannot recover power that became heat in the wire.
DC branch circuits 3 % Keeps loads inside their rated voltage window. Tighten to 2 % for LED lighting and sensitive electronics.

Why this calculator also checks ampacity

Most voltage drop calculators answer one question and stop. That leaves a genuine gap, because voltage drop being acceptable tells you nothing about whether the conductor is safe.

Take 10 AWG copper carrying 60 A over a 3 ft run at 48 V. The voltage drop is about 0.15 %, which any calculator will report as excellent. That conductor is also rated for 40 A in the 90 °C column of NEC Table 310.16, and 35 A at the 75 °C terminals most equipment uses. It is 25 A beyond its limit. It will run hot, cook its own insulation, and eventually fail — and every voltage-drop-only tool would have told the person it was fine.

So this tool runs both checks on the size you enter: the drop, and the two mandatory NEC ampacity tests from 690.8(B) or 210.19(A)(1), with ambient correction and conduit fill applied. If the conductor fails ampacity, that warning appears above the voltage drop result, because it is the more important answer.

The three levers, and which one to pull

When the drop is too high there are exactly three things you can change, and the calculator computes all three exactly for your circuit rather than describing them in general terms.

  1. A bigger conductor. The obvious lever and usually the most expensive. Drop is inversely proportional to conductor area, so doubling the area halves the drop — roughly three AWG sizes up.
  2. A shorter run. Directly proportional, so halving the distance halves the drop. Often free, if the equipment can move. Shifting an inverter three feet closer to a bank beats buying a size up in 4/0 cable.
  3. A higher system voltage. The strongest lever by far, and the one people overlook. Doubling the system voltage halves the current and doubles the volts you can afford to lose, so the drop falls by a factor of four on the same wire.

Voltage drop by wire size

Generated by the same engine as the calculator above, for a 20 ft one-way run in copper.

Voltage drop on a 12 V circuit over a 20 ft one-way run, copper.
12 V14121086421/0
5 A5.2%3.3%2.1%1.3%0.8%0.5%0.3%0.2%
10 A10.5%6.6%4.1%2.6%1.6%1.0%0.6%0.4%
20 A20.9%13.2%8.3%5.2%3.3%2.1%1.3%0.8%
30 A31.4%19.8%12.4%7.8%4.9%3.1%1.9%1.2%
50 A52.3%33.0%20.7%13.0%8.2%5.1%3.2%2.0%
Voltage drop on a 12 V circuit over a 20 ft one-way run, copper. Column headings are AWG. Green is 2 % or better, grey up to the 3 % the NEC informational note recommends, red above it. Voltage drop only — a size can look fine here and still fail NEC ampacity.
Voltage drop on a 24 V circuit over a 20 ft one-way run, copper.
24 V14121086421/0
5 A2.6%1.7%1.0%0.6%0.4%0.3%0.2%0.1%
10 A5.2%3.3%2.1%1.3%0.8%0.5%0.3%0.2%
20 A10.5%6.6%4.1%2.6%1.6%1.0%0.6%0.4%
30 A15.7%9.9%6.2%3.9%2.5%1.5%1.0%0.6%
50 A26.2%16.5%10.3%6.5%4.1%2.6%1.6%1.0%
Voltage drop on a 24 V circuit over a 20 ft one-way run, copper. Column headings are AWG. Green is 2 % or better, grey up to the 3 % the NEC informational note recommends, red above it. Voltage drop only — a size can look fine here and still fail NEC ampacity.
Voltage drop on a 48 V circuit over a 20 ft one-way run, copper.
48 V121086421/04/0
10 A1.7%1.0%0.6%0.4%0.3%0.2%0.1%0.1%
20 A3.3%2.1%1.3%0.8%0.5%0.3%0.2%0.1%
40 A6.6%4.1%2.6%1.6%1.0%0.6%0.4%0.2%
60 A9.9%6.2%3.9%2.5%1.5%1.0%0.6%0.3%
100 A16.5%10.3%6.5%4.1%2.6%1.6%1.0%0.5%
Voltage drop on a 48 V circuit over a 20 ft one-way run, copper. Column headings are AWG. Green is 2 % or better, grey up to the 3 % the NEC informational note recommends, red above it. Voltage drop only — a size can look fine here and still fail NEC ampacity.

What high voltage drop actually does

Nothing burns. That is what makes it insidious — an undersized-for-drop system works, just never quite right, and the symptoms rarely point at the wiring.

  • Batteries that never reach full. Drop on the controller-to-battery run means the controller sees a higher voltage than the bank actually has, ends absorption early and leaves it chronically undercharged. On lead-acid this causes sulfation and permanent capacity loss.
  • Inverters cutting out early. Under load, drop on the battery cable pulls the voltage the inverter sees below its cutoff while the bank still has usable capacity. It looks like a battery problem and is not.
  • Weak motor starts. Inrush current is several times running current, so the bus sags exactly when a compressor or pump needs it most.
  • Heat where you cannot see it. The lost power goes somewhere. On a high-current run that means a warm cable inside a conduit or a wall.

Frequently asked questions

What is an acceptable voltage drop for a solar system?

Three percent or less is the general design target, from NEC 210.19(A) Informational Note 4 and 215.2(A)(2) Informational Note 2, which recommend 3 % on a branch circuit or feeder and 5 % total. These are informational notes, which means advisory rather than enforceable. On the two circuits that matter most in an off-grid system — charge controller to battery, and battery to inverter — most designers and manufacturers specify 2 % or tighter, because those runs are short and the cost of the tighter target is usually one cable size.

Does low voltage drop mean my wire is safe?

No, and this is the most dangerous misconception in DIY solar wiring. Voltage drop and ampacity are completely separate checks. A 10 AWG conductor carrying 60 A over three feet has a voltage drop well under 1 %, and it is also roughly 25 A beyond its NEC limit — it will overheat and degrade its insulation. Voltage drop tells you whether your equipment will work properly. Ampacity tells you whether your wire will start a fire. This calculator runs both.

Do I use one-way or round-trip length?

Enter the one-way distance, measured along the route the cable actually takes. The calculator doubles it internally, because current flows out on one conductor and back on the other. Entering the round-trip figure yourself doubles it twice and roughly doubles the wire you think you need.

Why does the same wire drop four times more voltage at 12V than at 24V?

Two effects multiply. Moving the same power at half the voltage doubles the current, and voltage drop is proportional to current — so the drop in volts doubles. At the same time a fixed percentage of a lower voltage is fewer volts to spend, so your budget halves. Two times the loss against half the allowance is four times the problem. This is the strongest argument for building larger systems at 24 V or 48 V.

Does voltage drop waste energy, or just reduce voltage?

Both, and they are the same number. The voltage lost in a conductor is dissipated as heat, and the fraction of power lost equals the voltage drop percentage exactly. A run with 5 % voltage drop is turning 5 % of the power passing through it into heat. On a 1000 W circuit that is 50 W of continuous heating inside your wall or conduit.

Can I use this for AC circuits?

No. This calculator uses the DC resistance values in NEC Chapter 9, Table 8. AC voltage drop additionally involves conductor reactance and the load power factor, neither of which is modelled here. Use it for PV strings, charge controller runs, battery cables and DC loads — not for the AC output of an inverter or a household branch circuit.

Last reviewed 2026-08-19. Calculations reference NFPA 70 (NEC) 2023 where a code section applies. Sources, and what these tools deliberately do not model.