Skip to main content
SolarCalcWorks

12V Solar Wire Size Calculator

On a 12 volt system a 3 % voltage drop budget is only 0.36 volts, so the run length usually decides your wire long before ampacity does. Enter your current and distance and the calculator shows which of the three checks is actually forcing the size.

  • Locked to 12 V
  • NEC ampacity and voltage drop
  • RV, van, marine and off-grid
  • Full working shown

12V Solar Wire Size Calculator

Inputs3 % target
Conductor material

3% of 12 V = 0.36 V of budget across the whole round trip.

Installation conditionsdefaults are code-safe

Already have wire? Check the drop on a size you own.

Conductor13.3 mm²

6AWG · Cu · 90 °C

Voltage drop sets this size

Ampacity alone would allow 12 AWG. Holding the drop at or below 3.0% is what forces 6 AWG. A shorter run or a higher system voltage makes this cheaper; more copper is the expensive fix.

Voltage drop
2.46%
0.29 V lost
At the load
11.71 V
from 12 V
Amps at terminals
65 A
needs 25 A
Heat in the wire
5.9 W
at 20 A
Calculation

1Maximum circuit current

20 A rated

No 690.8(A) multiplier applies outside PV source and output circuits.

2Test A — 125 % at the terminals

20 A × 1.25 = 25 A required
6 AWG @ 75 °C = 65 A ✓

Continuous loads need 125 % headroom, and NEC 110.14(C) caps the usable column at the lowest-rated termination. No derating applies to this test.

3Test B — derated ampacity

75 A @ 90 °C = 75 A
must be ≥ 20 A ✓

30 °C ambient falls in the 26–30 °C band of Table 310.15(B)(1).

4Test C — can a device protect it?

device needed = 25 A (NEC 240.6(A))
6 AWG may be protected at up to 70 A ✓

NEC 240.4(B) permits rounding up to the next standard rating; 240.4(D) then caps 14, 12 and 10 AWG regardless — except on PV circuit conductors, which 240.4(G) exempts. A conductor with adequate ampacity can still fail here.

5Voltage drop

2 × 15.0 ft × 20 A × 0.4910 Ω/kft ÷ 1000
= 0.29 V = 2.46% of 12 V

The run is doubled because current returns on the second conductor. Resistance from NEC Chapter 9, Table 8. Voltage drop is a design target, not a code requirement — NEC 210.19(A) Informational Note 4 recommends 3 % or less.

6The answer

Ampacity needs 12 AWG, protection coordination needs 10 AWG, and the 3.0% drop target needs 6 AWG. The conductor has to satisfy all three, so the answer is the largest: 6 AWG.

Reference 210.19(A)(1) · 310.15 · 110.14(C) · 240.4 · Ch.9 T.8 — NEC 2023. Sources and limitations.

Overcurrent protection25 A

Calculated minimum 25 A, rounded up to the 25 A standard rating in NEC 240.6(A).

NEC 210.20(A): the device rating must be at least 125 % of the continuous load. NEC 240.4(D) additionally caps the device on 14, 12 and 10 AWG conductors.

NextSize the fuse or breaker for this circuitA conductor is only protected once a device is sized to it.
Nearby sizes20 A · 15 ft
Conductor sizes compared by ampacity margin and voltage drop
SizeAmps spareDropVerdict
10 AWG106.2%Drop too high
8 AWG253.9%Drop too high
6 AWGpick402.5%Meets all
4 AWG601.5%Meets all
3 AWG751.2%Meets all
2 AWG901.0%Meets all

Amps spare is the margin on the tighter of the two NEC ampacity tests.

Why 12 volt systems need so much copper

Voltage drop is calculated as a percentage of your system voltage, and 12 V leaves very little to give away. A 3 % budget on a 48 V bank is 1.44 V. The same 3 % on 12 V is 0.36 V — about a third of a volt to spend across the entire round trip. Two percent, the target for charge and inverter circuits, is 0.24 V.

For comparison, a single marginal crimp can eat a tenth of that budget on its own. This is why 12 V systems are unforgiving of runs that look trivially short on a drawing.

It gets worse, because moving the same power at a quarter of the voltage means four times the current, and voltage drop scales with current. Four times the current spent against a quarter of the budget means roughly sixteen times the conductor area to move the same watts the same distance.

12V wire size chart

Generated by the calculator engine at a 3 % voltage drop target, copper conductors, 90 °C insulation on 75 °C terminals, in conduit at 30 °C.

12V DC wire size by current and one-way run length.
12 V5 ft10 ft15 ft20 ft30 ft
5 A14 AWG14 AWG12 AWG10 AWG8 AWG
10 A14 AWG10 AWG8 AWG8 AWG6 AWG
15 A12 AWG8 AWG8 AWG6 AWG4 AWG
20 A10 AWG8 AWG6 AWG4 AWG3 AWG
30 A8 AWG6 AWG4 AWG3 AWG2 AWG
40 A8 AWG4 AWG3 AWG2 AWG1/0 AWG
60 A4 AWG3 AWG2 AWG1/0 AWG2/0 AWG
12V DC wire size by current and one-way run length. Copper, 90 °C insulation on 75 °C terminals, in conduit at 30 °C, two current-carrying conductors, 3 % drop target.Amber means voltage drop rather than ampacity forced that size. Run lengths are one-way.

Almost every cell is amber, meaning voltage drop rather than ampacity forced the size. On 12 V that is the normal case, not the exception.

The circuits in a typical 12V build

Panel to charge controller. Usually the longest run, and on small systems the panels are often wired in series to raise string voltage, which makes this run cheap. A two-panel series string at around 40 V behaves like a 40 V circuit for voltage drop purposes, not a 12 V one — enter the string’s operating voltage, not the battery voltage.

Charge controller to battery. Short and high current. Keep this at 2 % or better: the controller senses battery voltage at its own terminals, so drop on this run makes it read high, end absorption early and chronically undercharge the bank. This is one of the most common causes of “my batteries never seem to fill up”.

Battery to inverter. The highest current circuit in the whole system. A 2000 W inverter at 12 V pulls roughly 185 A at full output. Keep it short, keep it fused at the battery, and size it at 2 % or tighter.

DC branch circuits. Lights, fans, pumps, the fridge. Individually small, but they are usually the longest runs in a vehicle, and they are where dimming and slow pumps show up.

Wire types for 12V mobile installations

Vehicle and marine work has requirements a house does not. Vibration fatigues solid and coarse-stranded conductors, so use finely stranded cable throughout. In boats, tinned copper resists the corrosion untinned copper suffers in salt air, and it is worth the premium in any humid environment.

Welding cable is popular for battery runs because it is very flexible and cheap per amp, but it is generally not listed as a building wire and an inspector can reject it in a permitted installation. Its flexibility does not change the physics — size it with exactly the same rules.

Frequently asked questions

What gauge wire do I need for a 12V 100W solar panel?

A 100 W panel at 12 V produces roughly 5.5 to 6 A. Ampacity alone would be satisfied by 14 AWG. Voltage drop is the real constraint: at 10 ft one way, 14 AWG drops about 1.9 %, which is fine. At 25 ft it drops 4.6 %, and you need 10 AWG to stay under 3 %. Panel wattage sets the current, but distance sets the wire.

Can I use 12 gauge wire for a 30 amp 12V circuit?

No. NEC 240.4(D) caps 12 AWG copper at a 20 A overcurrent device, and a 30 A continuous circuit needs a 40 A device, so 12 AWG is not legal regardless of ampacity. Voltage drop is worse still — 12 AWG at 30 A drops 3 % of 12 V in under 4 ft of one-way run. A 30 A 12 V circuit of any useful length wants 8 AWG or larger.

Why does my 12V fridge run but my lights dim when it starts?

That is voltage drop under load. Compressor inrush current can be three to five times its running current for a fraction of a second, and voltage drop is proportional to current. If the shared feeder is marginal, that inrush pulls the whole bus down momentarily. Sizing the feeder to hold 2 % at running current usually removes the symptom entirely.

Is 12V or 24V better for a van or RV build?

12 V wins on component availability — nearly every RV appliance, fan, pump and light is sold as 12 V. 24 V wins on wiring: half the current for the same power means roughly a quarter of the voltage drop, so cable runs get dramatically cheaper. The practical rule is that under about 1500 W of continuous inverter load, 12 V is fine and simpler. Above that, the copper savings start to pay for the DC-DC converter your 12 V appliances will need.

How far can I run 12V wire?

Further than you think at low current and much shorter than you think at high current, because the limit scales with both. At 5 A, 10 AWG holds 3 % for about 29 ft one way. At 30 A the same wire manages under 5 ft. The calculator gives you the exact distance for your figures rather than a rule of thumb that only works at one current.

Last reviewed 2026-08-19. Calculations reference NFPA 70 (NEC) 2023 where a code section applies. Sources, and what these tools deliberately do not model.