How solar wire sizing actually works
A conductor has to pass three independent tests, and the wire you buy is whichever demands the most copper. Most calculators run one and ignore the others, which is why they disagree with each other.
Test 1 — ampacity: will it overheat?
Mandatory. The NEC publishes an allowable ampacity for every conductor size in Table 310.16 for conductors in a raceway or cable, and Table 310.17 for single conductors in free air. Both assume a 30 °C (86 °F) ambient, and both get modified by where you actually install the wire.
For a solar circuit the NEC states the requirement as two conditions that must both hold — 690.8(B) for PV circuits, 210.19(A)(1) for branch circuits, worded almost identically:
- Before derating: the table ampacity, read in the column matching the lowest-rated termination, must be at least 125 % of the maximum circuit current. NEC 110.14(C) is what caps you to that column — a 90 °C wire landing on a 75 °C lug is a 75 °C circuit at that point.
- After derating: the table ampacity, read in the column matching the conductor’s own insulation rating, then multiplied by the ambient correction factor from Table 310.15(B)(1) and the fill adjustment from Table 310.15(C)(1), must be at least the maximum circuit current.
Applying 125 % and the derates to the same number in one step — a common shortcut — overstates the requirement and sells people wire they do not need.
Test 2 — can a device actually protect it?
This is the check almost nobody runs, and it changes real answers. NEC 240.4 requires a conductor to be protected in accordance with its ampacity, and 240.4(D) caps the device on 14, 12 and 10 AWG regardless of what the ampacity table says.
A 20 A continuous load needs a 25 A device under 210.20(A). 12 AWG copper carries 25 A at 75 °C, so it passes both ampacity tests — but 240.4(D) caps its device at 20 A. The pairing is illegal, and a calculator that stops at ampacity will happily recommend it.
Test 3 — voltage drop: will the load still work?
Every conductor has resistance, so some voltage is lost as heat on the way to the load:
Vdrop = 2 × L × I × R ÷ 1000 — where L is the one-way length in feet, I the current in amps, and R the resistance in ohms per 1000 ft
The 2 is there because the current has to come back. R comes from NEC Chapter 9, Table 8, which publishes DC resistance directly — meaning DC voltage drop is exactly computable, with no power factor or reactance term to estimate.
Unlike ampacity, this is not a code requirement. It is a design target, and on low-voltage DC it is usually the target that decides your wire.
Why 12 V systems eat so much copper
A 3 % drop is 3 % of whatever your system voltage is. On a 48 V bank that is 1.44 V of budget. On 12 V it is 0.36 V — one quarter of the allowance.
It compounds, because moving the same power at a quarter of the voltage means four times the current, and drop is proportional to current. Four times the current across a quarter of the budget means roughly sixteen times the conductor area for the same watts over the same distance.
Common solar wire sizes
Generated by the same engine as the calculator above, so they cannot drift out of sync with it.
12 V DC circuits
| 12 V | 5 ft | 10 ft | 15 ft | 25 ft | 40 ft |
|---|---|---|---|---|---|
| 5 A | 14 AWG | 14 AWG | 12 AWG | 10 AWG | 8 AWG |
| 10 A | 14 AWG | 10 AWG | 8 AWG | 6 AWG | 4 AWG |
| 20 A | 10 AWG | 8 AWG | 6 AWG | 4 AWG | 2 AWG |
| 30 A | 8 AWG | 6 AWG | 4 AWG | 2 AWG | 1/0 AWG |
| 50 A | 6 AWG | 4 AWG | 2 AWG | 1/0 AWG | 3/0 AWG |
| 80 A | 3 AWG | 2 AWG | 1/0 AWG | 3/0 AWG | 250 kcmil |
24 V DC circuits
| 24 V | 10 ft | 20 ft | 30 ft | 50 ft | 75 ft |
|---|---|---|---|---|---|
| 5 A | 14 AWG | 14 AWG | 12 AWG | 10 AWG | 8 AWG |
| 10 A | 14 AWG | 10 AWG | 8 AWG | 6 AWG | 4 AWG |
| 20 A | 10 AWG | 8 AWG | 6 AWG | 4 AWG | 2 AWG |
| 30 A | 8 AWG | 6 AWG | 4 AWG | 2 AWG | 1 AWG |
| 50 A | 6 AWG | 4 AWG | 2 AWG | 1/0 AWG | 3/0 AWG |
| 80 A | 3 AWG | 2 AWG | 1/0 AWG | 3/0 AWG | 250 kcmil |
48 V DC circuits
| 48 V | 10 ft | 25 ft | 50 ft | 75 ft | 100 ft |
|---|---|---|---|---|---|
| 10 A | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 6 AWG |
| 20 A | 10 AWG | 10 AWG | 6 AWG | 4 AWG | 4 AWG |
| 30 A | 8 AWG | 8 AWG | 4 AWG | 4 AWG | 2 AWG |
| 50 A | 6 AWG | 6 AWG | 3 AWG | 1 AWG | 1/0 AWG |
| 80 A | 3 AWG | 3 AWG | 1 AWG | 2/0 AWG | 3/0 AWG |
| 120 A | 1/0 AWG | 1/0 AWG | 2/0 AWG | 3/0 AWG | 250 kcmil |
A worked example you can check by hand
A 2000 W 12 V inverter at 90 % efficiency draws 2000 ÷ 0.9 ÷ 12, about 185 A at full output. The battery sits 6 ft away. What cable does it need?
Ampacity. Inverter load is continuous, so 185 A × 1.25 = 231.25 A required at the 75 °C terminals. In Table 310.16, 4/0 AWG copper at 75 °C is 230 A — 1.25 A short. 250 kcmil at 255 A clears it.
Voltage drop. A 2 % target on 12 V is 0.24 V. For 4/0 AWG:
2 × 6 ft × 185 A × 0.0608 Ω/1000 ft = 0.135 V = 1.12 % — passes
4/0 passes voltage drop easily. Ampacity forces the size up to 250 kcmil, and no amount of shortening the run will change that — exactly the distinction the result panel calls out.
This is also why serious off-grid systems are built at 48 V. The same 2000 W at 48 V is 46 A, and 6 AWG handles it.
Which wire type to use where
Ampacity tables assume a conductor listed for the environment it is in. The insulation matters as much as the gauge.
| Where | Typical type | Why |
|---|---|---|
| Between modules, exposed under the array | PV Wire or USE-2 | Sunlight resistant, 90 °C wet, required by NEC 690.31(C) for exposed single-conductor runs. |
| In conduit, outdoors or underground | THWN-2 or XHHW-2 | 90 °C wet rating. Plain THHN is not rated for wet locations. |
| In conduit, indoors and dry | THHN | 90 °C dry. The usual choice inside a building. |
| Battery to inverter | Listed battery cable, RHW-2 or THW-2 | Fine stranding survives vibration and tight bends. Welding cable is common in RV work but is generally not listed as building wire. |
Mistakes that cost people money
- Entering round-trip length. The calculator doubles the one-way figure for you.
- Sizing to the fuse instead of the load. The conductor is sized to the circuit current; the device is then sized to protect that conductor. Backwards leads to conductors no device can legally protect.
- Ignoring the termination rating. A 90 °C conductor on 75 °C lugs is limited to the 75 °C column at those lugs. The 90 °C rating still earns its keep — it is the column used for derating.
- Forgetting the rooftop adder. Conduit in direct sun within 3/4 in. of a roof takes a 33 °C adder under NEC 310.15(B)(2). On a 40 °C day that is 73 °C, where even 90 °C wire loses half its ampacity.
- Counting grounding conductors in the fill. Equipment grounding conductors are not current-carrying and are excluded under 310.15(E).
