Skip to main content
SolarCalcWorks

Solar Fuse & Breaker Size Calculator

Size the overcurrent device for any solar DC circuit, and check that it can legally protect the conductor it sits on. Those are two different requirements, and a device that satisfies one while failing the other is the most common way a DIY solar install fails inspection.

  • NEC 690.9(B) and 240.6(A)
  • Conductor coordination checked
  • Module series fuse rating check
  • PV, battery and controller circuits

Solar Fuse Size Calculator

Inputs
Conductor material
Installation conditionsdefaults are code-safe

These affect the conductor's ampacity, which is what determines the largest device allowed to protect it.

Overcurrent devicemin 125 A

125A · DC-rated

Why this rating

NEC 210.20(A): the device must be rated at least 125 % of the continuous load it serves.

Circuit current
100 A
as entered
Minimum device
125 A
125 % of the above
Standard rating
125 A
NEC 240.6(A)
Smallest conductor
1 AWG
this device can protect
  • Note1 AWG is the smallest conductor a 125 A device can protect under these conditions.
  • NoteA DC circuit needs a device listed for DC at or above the circuit voltage. An AC-only breaker will not reliably interrupt a DC fault, because there is no current zero-crossing to help extinguish the arc.
Calculation

1Maximum circuit current

100 A rated circuit current

No 690.8(A) multiplier applies outside PV source and output circuits.

2Minimum device rating

100 A × 1.25 = 125 A
next standard rating in 240.6(A) = 125 A

NEC 210.20(A): the device must be rated at least 125 % of the continuous load it serves.

3Can that device protect the conductor?

Pick the conductor above and this step checks the pairing. Without it the device rating is correct but unverified against anything.

Reference 210.19(A)(1) · 210.20(A) · 240.6(A) · 240.4(B) · 240.4(D) — NEC 2023. Sources and limitations.

NextSize the conductor this device protectsA device rating only means something against a conductor that can carry the current.

Two requirements, not one

An overcurrent device has to satisfy two separate things at once, and most sizing guides only cover the first.

It must be large enough to carry the circuit. NEC 690.9(B) for PV circuits and NEC 210.20(A) for branch circuits both require at least 125 % of the maximum or continuous current. A device sized exactly to the load nuisance-trips.

It must be small enough to protect the conductor. NEC 240.4 requires the conductor to be protected in accordance with its ampacity. Two qualifications matter:

  • 240.4(B) permits rounding up to the next standard rating where the conductor’s ampacity does not itself land on one, for devices up to 800 A.
  • 240.4(D) caps the device on 14, 12 and 10 AWG regardless — 15 A, 20 A and 30 A for copper.

Those two requirements can conflict. A 20 A continuous load needs a 25 A device, and 12 AWG copper carries 25 A at 75 °C — but 240.4(D) caps its device at 20 A, so that pairing is illegal and you need 10 AWG. The calculator refuses the combination rather than quietly returning a number.

The module series fuse rating

This is the check that most solar fuse calculators leave out entirely, and it can only bite you in one direction: too large.

Every module datasheet carries a maximum series fuse rating, typically between 15 and 30 A. It exists because the module’s own conductors and bypass diodes can only survive so much fault current back-fed from the other parallel strings. NEC 690.9(B) tells you the smallest device permitted; the module tells you the largest. If the two ranges do not overlap, the array needs rewiring — fewer strings per fuse, or a fuse per string — not a bigger fuse.

Enter it above whenever you are sizing a PV source circuit. The calculator will confirm the device fits inside it, or refuse and explain why.

Standard device ratings

NEC 240.6(A) lists the standard ampere ratings. You round up to one of these, never down and never to an arbitrary value:

15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600 A — plus the additional standard fuse ratings of 1, 3, 6, 10 and 601 A.

Fuse types used in solar

Type Where Note
Class T Battery to inverter High interrupting rating, typically 20 kA. The usual choice on lithium banks, which can deliver enormous fault current.
ANL / MEGA Battery and high-current DC Common in RV and marine work. Lower interrupting rating than Class T — check it against your bank.
MidiVal / MIDI Branch circuits up to about 200 A Compact, widely available.
Inline blade Small DC branch circuits Fine for lighting and pumps at modest current.
PV string fuse (gPV) Combiner boxes Listed specifically for PV, rated for DC and for the string voltage.
DC-rated breaker Anywhere a switch is useful Must be listed for DC at your circuit voltage. Doubles as a disconnect.

Interrupting rating matters as much as the ampere rating. A device has to be able to break the fault current available at that point without failing. A lithium bank can deliver several thousand amps into a dead short, which is beyond what many inexpensive fuses can safely interrupt. That figure is on the device datasheet, and this calculator does not compute available fault current — it is a system-specific number that depends on your battery and your cable.

Where devices go

At the source of fault current, as close as practical. On a battery circuit that is the battery positive terminal. On a PV circuit it is the combiner box. The point is that the device protects everything downstream of it, so anything upstream of the device is unprotected cable.

A common and dangerous shortcut is fusing at the inverter or the load end. That leaves the entire run exposed to a short to the chassis or the enclosure, which in a metal-bodied vehicle or a metal enclosure is the most likely fault of all.

Frequently asked questions

What size fuse do I need between my battery and inverter?

Start from the inverter's continuous DC input current, not its AC watts. A 3000 W inverter at 90 % efficiency on a 24 V bank draws roughly 145 A, so the device must be at least 145 × 1.25 = 181 A, which rounds up to a 200 A standard rating. Then check that your cable can be protected at 200 A — this calculator does both. Class T fuses are the usual choice on lithium banks because of their high interrupting rating.

Why is the fuse bigger than my circuit current?

Because it is not protecting the load, it is protecting the conductor, and it has to carry the circuit's continuous current indefinitely without nuisance-tripping. NEC 210.20(A) and 690.9(B) both require the device to be rated at least 125 % of the continuous or maximum circuit current. A device sized exactly to the load would trip on normal operation.

What is the module maximum series fuse rating?

A figure on the module datasheet, usually 15 to 30 A, that limits the largest fuse permitted in series with that module. It exists because a module's own conductors and bypass diodes can only survive so much back-fed fault current from parallel strings. NEC 690.9(B) sets the minimum device size; this rating sets a maximum the code does not license you to exceed. The calculator checks both.

Do I need a fuse for every solar panel string?

Two or fewer parallel strings usually need none, because with only one other string able to back-feed a fault, the fault current cannot exceed what the conductors already carry. Three or more parallel strings generally do need a fuse per string. This is why combiner boxes exist and why they come with fuse holders.

Can I use an AC breaker on a DC circuit?

No. Alternating current crosses zero 120 times a second, which helps extinguish the arc when contacts open. Direct current never does, so a DC arc sustains itself and an AC-only device can fail to interrupt the fault — sometimes catastrophically. Use a device listed for DC at or above your circuit voltage, and for PV circuits one listed for use in PV systems.

Where should the fuse go?

As close to the source of fault current as practical. On a battery circuit that means at the battery's positive terminal, because the battery is what can deliver thousands of amps into a short. A fuse at the far end leaves the whole cable run unprotected against exactly the fault it is most likely to see.

Last reviewed 2026-08-19. Calculations reference NFPA 70 (NEC) 2023 where a code section applies. Sources, and what these tools deliberately do not model.