Skip to main content
SolarCalcWorks

RV & Camper Solar Wire Size Calculator

Size the wiring for an RV, van or trailer solar build. The electrical rules are the same NEC ampacity and voltage drop maths as a house, but a vehicle adds vibration, tight bends, heat and a 12 volt bus that punishes every extra foot of cable.

  • Built around 12 V vehicle systems
  • Vibration and stranding guidance
  • NEC ampacity and voltage drop
  • Fridge, pump, inverter and array runs

RV Solar Wire Size Calculator

Inputs3 % target
System voltage
Conductor material

3% of 12 V = 0.36 V of budget across the whole round trip.

Installation conditionsdefaults are code-safe

Already have wire? Check the drop on a size you own.

Conductor21.1 mm²

4AWG · Cu · 90 °C

Voltage drop sets this size

Ampacity alone would allow 12 AWG. Holding the drop at or below 3.0% is what forces 4 AWG. A shorter run or a higher system voltage makes this cheaper; more copper is the expensive fix.

Voltage drop
2.05%
0.25 V lost
At the load
11.75 V
from 12 V
Amps at terminals
85 A
needs 25 A
Heat in the wire
4.9 W
at 20 A
Calculation

1Maximum circuit current

20 A rated

No 690.8(A) multiplier applies outside PV source and output circuits.

2Test A — 125 % at the terminals

20 A × 1.25 = 25 A required
4 AWG @ 75 °C = 85 A ✓

Continuous loads need 125 % headroom, and NEC 110.14(C) caps the usable column at the lowest-rated termination. No derating applies to this test.

3Test B — derated ampacity

95 A @ 90 °C = 95 A
must be ≥ 20 A ✓

30 °C ambient falls in the 26–30 °C band of Table 310.15(B)(1).

4Test C — can a device protect it?

device needed = 25 A (NEC 240.6(A))
4 AWG may be protected at up to 90 A ✓

NEC 240.4(B) permits rounding up to the next standard rating; 240.4(D) then caps 14, 12 and 10 AWG regardless — except on PV circuit conductors, which 240.4(G) exempts. A conductor with adequate ampacity can still fail here.

5Voltage drop

2 × 20.0 ft × 20 A × 0.3080 Ω/kft ÷ 1000
= 0.25 V = 2.05% of 12 V

The run is doubled because current returns on the second conductor. Resistance from NEC Chapter 9, Table 8. Voltage drop is a design target, not a code requirement — NEC 210.19(A) Informational Note 4 recommends 3 % or less.

6The answer

Ampacity needs 12 AWG, protection coordination needs 10 AWG, and the 3.0% drop target needs 4 AWG. The conductor has to satisfy all three, so the answer is the largest: 4 AWG.

Reference 210.19(A)(1) · 310.15 · 110.14(C) · 240.4 · Ch.9 T.8 — NEC 2023. Sources and limitations.

Overcurrent protection25 A

Calculated minimum 25 A, rounded up to the 25 A standard rating in NEC 240.6(A).

NEC 210.20(A): the device rating must be at least 125 % of the continuous load. NEC 240.4(D) additionally caps the device on 14, 12 and 10 AWG conductors.

NextSize the fuse or breaker for this circuitA conductor is only protected once a device is sized to it.
Nearby sizes20 A · 20 ft
Conductor sizes compared by ampacity margin and voltage drop
SizeAmps spareDropVerdict
8 AWG255.2%Drop too high
6 AWG403.3%Drop too high
4 AWGpick602.1%Meets all
3 AWG751.6%Meets all
2 AWG901.3%Meets all
1 AWG1051.0%Meets all

Amps spare is the margin on the tighter of the two NEC ampacity tests.

What is different about a vehicle

The electrical maths does not change. A 12 V circuit in a van obeys the same NEC ampacity tables and the same voltage drop equation as a 12 V circuit in a cabin. What changes is everything around it.

Vibration. This is the big one. Solid conductors and coarse stranding work-harden under constant vibration until individual strands fracture — inside the insulation, where nothing is visible and the first symptom is a hot connection. Use finely stranded cable for everything, and welding-style or marine-grade cable for the battery runs.

Distance versus voltage. A van looks small until you route a cable. A fridge at the back, a charge controller under a bed and an inverter near the batteries can easily total 15 to 20 ft one way. At 12 V that is enough to force two or three sizes up.

Heat. Cables run behind panelling, above a fridge compressor, or through a sealed battery box in July. The NEC ampacity tables assume 30 °C. A sealed compartment in summer is not 30 °C, and the installation conditions panel is there for that.

Movement and abrasion. Every point where a cable passes through metal needs a grommet, and every run needs securing. Chafe is the most common cause of vehicle electrical fires.

Sizing the circuits in a typical build

12V DC wire size for typical RV circuit currents and run lengths.
12 V5 ft10 ft15 ft20 ft30 ft
5 A14 AWG14 AWG12 AWG10 AWG8 AWG
10 A14 AWG10 AWG8 AWG8 AWG6 AWG
15 A12 AWG8 AWG8 AWG6 AWG4 AWG
20 A10 AWG8 AWG6 AWG4 AWG3 AWG
30 A8 AWG6 AWG4 AWG3 AWG2 AWG
50 A6 AWG4 AWG2 AWG1 AWG2/0 AWG
12V DC wire size for typical RV circuit currents and run lengths. Copper, 90 °C insulation on 75 °C terminals, in conduit at 30 °C, two current-carrying conductors, 3 % drop target.Amber means voltage drop rather than ampacity forced that size. Run lengths are one-way.

Roof array to charge controller. Often the longest run in the vehicle. Wire the panels in series where the controller allows it: series raises string voltage and leaves current alone, which makes this run dramatically cheaper. A two-panel series string at 40 V behaves like a 40 V circuit for voltage drop, not a 12 V one — enter the string voltage, not the battery voltage.

Controller to battery. Short, high current, and the one people get wrong. The controller senses battery voltage at its own terminals, so drop here makes it read high, end absorption early, and leave the bank chronically undercharged. Target 2 %.

Battery to inverter. The highest current in the vehicle. A 2000 W inverter on a 12 V bank draws around 185 A. Mount the inverter as close to the batteries as the layout allows — moving it three feet closer usually saves more than a cable size increase costs.

Branch circuits. Lights, fans, pump, fridge. Small currents, long runs, and where dimming shows up.

Cable types worth knowing

Welding cable is extremely flexible and cheap per amp, which is why it is everywhere in van builds. It is generally not listed as a building wire, so it can be rejected in a permitted installation, but in a vehicle that is usually not the governing standard. It does not change the physics — size it identically.

Marine-grade tinned copper costs more and resists corrosion far better in humid or salt environments. In a van that sees coastal weather or condensation, it is money well spent.

Duplex and triplex cable bundles conductors in a single jacket, which is neater and reduces chafe points. Remember that bundled current-carrying conductors count toward the NEC 310.15(C)(1) fill adjustment once there are four or more.

Where to go next

Sizing individual circuits is the last step of a van electrical design, not the first. Work out your daily consumption, then the bank, then the array, then the inverter — each one produces the current figure the next calculator needs.

Frequently asked questions

What wire size do I need for 400W of solar on my RV?

It depends on where you measure. Wired as two series pairs the array runs near 40 V and draws about 10 A, which 10 AWG handles over any realistic roof run. But the output of the charge controller into a 12 V bank is roughly 30 A, and that short run wants 8 AWG or larger to stay inside 2 %. Size each segment separately — the array run and the controller output are different circuits with very different currents.

Can I use regular house wire in a camper?

Not for anything that moves or vibrates. Solid and coarse-stranded building wire work-hardens under vibration until strands fracture, usually inside the insulation where you cannot see it. Use finely stranded cable throughout a vehicle. THHN in conduit is acceptable for fixed runs inside a coach, but battery and inverter cables should be flexible types.

Do RV solar systems have to follow the NEC?

A recreational vehicle is covered by NEC Article 551 and by NFPA 1192, and manufactured units are typically built to RVIA standards, not by treating the coach as a small house. Ampacity and voltage drop physics are identical, which is what this calculator computes, but the wiring methods, connectors and inspection regime differ. If the vehicle is registered and insured, check what your insurer and jurisdiction expect before finalising a design.

How do I work out my daily current for a van build?

List every load with its watts and the hours per day it actually runs, multiply, and add the results. A 45 W fridge running 10 hours is 450 Wh; four 5 W lights for 4 hours is 80 Wh. The calculator on this page sizes individual circuits — for the bank and array that supply them, use the battery bank and array size calculators.

Why do my lights dim when the water pump runs?

A shared feeder that is marginal for voltage drop. Pump and compressor inrush is several times running current for a fraction of a second, and drop scales with current, so the bus sags hardest exactly when a motor starts. Size the shared feeder to hold 2 % at running current and the symptom generally disappears.

Last reviewed 2026-08-19. Calculations reference NFPA 70 (NEC) 2023 where a code section applies. Sources, and what these tools deliberately do not model.